- The packing height determines the volume of sealing modules that shall be utilized in a frame opening. Correct utilization of the packing height is crucial for certified product performance.
- The packing height (h) as presented in the table equals the inner height of the frame opening (H) minus the required space in mm for the compression unit
- The combined height of the chosen sealing modules must always correspond to the packing height (h)
- Calculate the correct packing height according to installation instructions before selecting sealing modules
Measured in millimeters (mm) |
Frame height (H) [mm] | Packing height (h) [mm] | Frame size |
101 | 60 | 1 and 2 |
160 | 120 | 3 and 4 |
218 | 180 | 5 and 6 |
278 | 240 | 7 and 8 |